Permit Review Detail
Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T03OT01981
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/17/2003 | Blanca Espino | ENGINEERING | REVIEW | Denied | 1. Hydrology Report required. Provide an encroachment analysis. The proposed structures can not increase the base flood elevation by more than .1 foot. Tucson Code Chapter 26 Section 5.2 (5) 2. The Hydrology Report must determine the minimum finish floor elevation (FFE) for the detached structure (the garage). The minimum FFE must be one foot above the base flood elevation. Tucson Code Chapter 26 Section 5.2 (9) 3. It appears that the cost estimate for the improvements to the existing non-conforming structure is too low. Current cost of new construction is approximately $60 per square foot. Provide a detailed cost estimate for the value of all proposed improvements to the existing structure by a licensed contractor. The estimate will be evaluated for completeness and reasonableness and must be in line with current construction costs. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/09/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 12/09/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |