Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T03OT01858
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/12/2003 | Loren Makus | ENGINEERING | REVIEW | Denied | DATE: November 14, 2003 TO: Phil Swaim SUBJECT: Clements Center Phase II, Floodplain Use Permit REVIEWER: Loren Makus ACTIVITY NUMBER: T03OT01858 SUMMARY: The Floodplain Use Permit application and Drainage Report were reviewed by Development Services Department Engineering Division. The Floodplain Use Permit can not be issued at this time. Please address the following comments. Drainage Report Comments: 1. Revise the drainage report to show freeboard calculations for the 100-year flows in the adjacent wash. The top of the cutoff wall must be at least as high as the required freeboard above the water surface elevation. 2. The cutoff wall must be designed and permitted as a retaining wall. Revise the Drainage Report to address these comments and resubmit two copies for review along with a $150 review fee. Include a letter explaining how each comment has been addressed. Loren Makus Senior Engineering Associate Engineering Division Development Services |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/20/2003 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 11/18/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |