Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03OT01813
Parcel: 13104399B

Address:
1747 S SWAN RD

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T03OT01813
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2004 JIM EGAN FIRE REVIEW Denied Fire hydrants required. Submit approved COT Water Plan.
01/23/2004 Loren Makus ENGINEERING REVIEW Approved A grading permit applicaton with stormwater pollution prevention plan is required.
01/28/2004 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next
Submittal, which states how all Zoning Review Section comments Regarding the Land Use Code and Development Standards were Addressed.
CODE SECTION/ DEVELOPMENT STANDARD

1. The case number (T03OT01816) noted on the cover sheet of the recorded covenant is incorrect. The correct case number is T03OT01813. Please re-record page 1 of 4 (cover sheet) of the lot combination covenant and submit the entire copy (pages 1-4) for DSD records.

2. The loading zone for the existing billboard located west of building 9 is inaccessible. Per Loren Makus, Engineering Section, please demonstrate maneuverability into/out of the loading zone.

3. The loading zone for the billboard located near the northwest corner of the site does not comply with LUC Sec. 3.4.4.1.B.3. The loading zone may not be located under the billboard, please revise.

4. Delete the striped pedestrian path located in front of the loading zone for the billboard located east of building 14. Per D.S. 2-08.4.1.F, a pedestrian path may not be located between a vehicle parking space (or loading zone) and the PAAL providing access to that space.

5. All requested changes must be made to the site and landscape plans. (D.S. 2-07.2.1.A)


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
01/29/2004 Joseph Linville LANDSCAPE REVIEW Denied 1) Revise the landscape plan to dimension the 10' wide street landscape border in the vicinity of the billboard located along Swan Road frontage. LUC 3.7.2.4.A
The loading zone and pavement cannot be located within the portion of landscape border located behind the screen wall.

2) Revise the site plan to locate the loading area screen wall along 29th Street behind the street landscape border, as shown on the landscape plan. LUC 3.7.3.2

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2004 LISA LESNY OUT TO CUSTOMER Completed