Permit Number: T03OT01795
Parcel: 137055150

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T03OT01795
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2003 JOE LINVILLE NPPO REVIEW Approved Exception
12/08/2003 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Pima Community College - Desert Vista Campus
REVIEWER: Doug Williams
DATE: 8 December 2003
ACTIVITY NUMBERS: T03OT01795/97 & T03BU02639

SUMMARY: Engineering Division has reviewed the drainage report, site, grading, floodplain use permit and stormwater pollution prevention plans. Approval of the Site and Grading Plans is not recommended at this time. The following comments must be addressed:

1. Section 26-11.2 i of the Tucson Code specifies a Floodplain Use Permit Fee for reviews of engineering studies, including review of (a) first resubmittal, of $150.00. This fee must be remitted prior to, or concurrent with a revised drainage report.

2. Please provide recording information for the abandonment of the existing 60' drainage easement for conveyance of flow associated with concentration point D14A. If not recorded, the easement must be abandoned with recording information provided on the plan prior to approval of a grading permit;

SWPPP COMMENTS:

Please provide an additional SWPPP submittal for stamping/approving and issuance purposes - only one copy was received with the resubmittal.

Please address the above comments. An over the counter review/approval may be arranged when the comments above have been addressed.

If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
12/15/2003 Patricia Gehlen HANDICAP-SITE REVIEW Denied Handi-cap
12/15/2003
Revise sheet C12 to include parking calculations. The calculations must include the number of parking spaces provided, the number of handicap spaces required and provided.
12/16/2003 JIM EGAN FIRE REVIEW Denied 1. Fire hydrant required. Submit APPROVED COT Water Plan.
2. Fire appratus access roadway must be provided and extended to within 150 feet of all portions of exterior walls of all structures. An approved turnaround must be provided for dead-end access roadways.