Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2003 PAUL MACHADO ENGINEERING REVIEW Denied To: Ron Diehl/Mike Bratton
5989 E. Grant Road, Ste. 101
Tucson, Arizona
SUBJECT: 8721 E. Honey Bear Place
Floodplain use permit T03OT00989 (First Review)
T13S, R15E, Section 34


RESUBMITTAL REQUIRED: Floodplain use permit


The Floodplain use permit (FUP) cannot be approved at this time. Please address the following review comments prior to the next submittal.

Floodplain Use Permit:

1. It appears that the building is not being constructed wihtin the building envelope per the Final Plat. Since the building is being placed further into the flood plain, a drainage report including an encroachment analysis along with a recommended FFE is required per S.M.D.D.F.M., chap. II, 2.1.3.
2. Please map the 100-year flood plain limits correctly. A copy of the Final Plat is included with the comments showing the location of both the 100-year and the EHS..
3. An elevation certificate is required to be submitted to COT engineering division for the Records dept. after construction of the building and before the final C of O is issued.


If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us

Paul Machado,
Senior Engineering Associate