Review Details: FLOODPLAIN

Permit Number - T03OT00947
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2003 Paul Machado ENGINEERING REVIEW Denied To: Joseph Smith
8727 E. Golf Links Road
Tucson, Arizona, 85710

SUBJECT: 9951 E. Millmar Road
Floodplain use permit T03OT00947
(Second Review)
T14S, R15E, Section 35

RESUBMITTAL REQUIRED: Floodplain use permit


The Floodplain use permit (FUP) cannot be approved at this time. Please address the following review comments prior to the next submittal.


Floodplain Use Permit:

1. It appears that the building is within the Erosion Hazard Setback of the Pantano Wash. The structure cannot be placed within the EHS. It was noted by recent field visit that the property may be adjacent to a curved section of the Pantano Wash. The 350' EHS may increase due to the curvature of the Pantano Wash. Please include setback calculations in a curve in the Pantano Wash, a regional water course, per S.M.D.D.F.M., chap. VII, 7.6. If the engineer can prove that the property is not adjacent to the curved section of the Pantano Wash, than the standard 350' setback will be allowed, however the position the building is in now is still within the 350' EHS and will be required to move further Southwest.
2. An elevation certificate is submitted to COT engineering division for the Records dept. after construction of the building. Per previous comment.

If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us

Paul Machado,
Senior Engineering Associate