Permit Number: T03OT00947
Parcel: 13631011D

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T03OT00947
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2003 PAUL MACHADO ENGINEERING REVIEW Denied To: Joseph Smith
8727 E. Golf Links Road
Tucson, Arizona, 85710

SUBJECT: 9951 E. Millmar Road
Floodplain use permit T03OT00947 (First Review)
T14S, R15E, Section 35

RESUBMITTAL REQUIRED: Floodplain use permit

The Floodplain use permit (FUP) cannot be approved at this time. Please address the following review comments prior to the next submittal.


Floodplain Use Permit:

1. It appears that the building is within the 350' erosion hazard setback of the Pantano Wash. Please delineate the top of bank to ensure proper measurement and show the erosion hazard setback.
2. An elevation certificate is submitted to COT engineering division for the Records dept. after construction of the building.
3. Please correct and complete the legal description on the elevation certificate. The survey is calling out that the lot number is 7 and the elevation certificate reads 9.


If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us

Paul Machado,
Senior Engineering Associate