Permit Number: T03OT00479
Parcel: 12104107A

Address:
5702 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T03OT00479
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2003 BLANCA ESPINO ENGINEERING REVIEW Denied 1. Indicate existing and future sight visibility triangles on Grant Road which are 345' Near side and 125' Far side but when there's a street median the SVT for the Far side is 30'. The SVT from Rainbow Vista Drive onto Grant Road is 340' Near side and 125' Far side. Correct and revise. D.S. 2-02.21A.10

2. Indicate limits of the 100-year floodplain and water surface elevation. As per FIRM Panel 1663K, the southwestern part of the site is in the FEMA floodplain Zone AH. D.S. 2-02.2.1.A.15

3. Indicate existing and future dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way. Indicate if there's a street median on Grant Road. D.S. 2-02.2.1.A.19

4. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways and utility lines. Future sidewalk area is 12' with a 6' wide sidewalk on Grant Road. D.S. 2-02.2.1.A.21
06/10/2003 JOE LINVILLE LANDSCAPE REVIEW Approved
06/16/2003 PETER MCLAUGHLIN ZONING REVIEW Approv-Cond SITE PLAN TRANSMITTAL

TO: Stephen Robinson
8115 E. Cloud Road
Tucson, AZ 85750
(520) 722-4635

FROM: Peter McLaughlin
Senior Planner
Development Services Dept.

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T03OT00479
5702 & 5704 E. Grant Road
Tucson, AZ
Site Plan Review

TRANSMITTAL: June 16, 2003

Upon completion of the following revision/addition, an over the counter review may be arranged to obtain stamped approval by the zoning review section without resubmitting the site plan. The following item must be revised on or added to the site plan:

1. This site is made up of two lots, which must be combined prior to site plan approval. Once the lot combination has been processed, provide the following documentation to the Zoning Review Section for review: notarized and recorded covenant and an approved Pima County tax combination form. A copy of the tax combo form and affidavit is attached to these review comments.

2. The adjacent zoning to the west is O-3. Please revise. DS 2-02.2.1.A.28



If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
06/16/2003 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2003 LISA LESNY OUT TO CUSTOMER Completed
06/17/2003 ANGIE SHOFFSTALL REJECT SHELF Completed