Permit Number: T03OT00356
Parcel: 13225047B

Address:
4790 S JULIAN AV

Review Status: Completed

Review Details: SITE

Permit Number - T03OT00356
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2003 JIM EGAN FIRE REVIEW Approved
03/07/2003 DOUG WILLIAMS FLOODPLAIN REVIEW Denied
03/07/2003 JOE LINVILLE LANDSCAPE REVIEW Denied
03/07/2003 JOE LINVILLE NPPO REVIEW Denied
03/07/2003 DAN CASTRO ZONING REVIEW Denied
03/07/2003 DAN CASTRO HANDICAP-SITE REVIEW Denied
03/07/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied See below:






SUBJECT: CEMROCK Expansion
REVIEWER: Doug Williams
DATE: 3 March 2003
ACTIVITY NUMBER: T03CM00507

SUMMARY: Engineering Division has reviewed the site plan received on February 22, 2003. Approval of the Site Plan is not recommended at this time. The following comments are offered:


SITE PLAN COMMENTS:

a) Provide a basis of bearing, per Development Standard (DS) 2-02.2.1.5.
b) Depict maneuverability area for the loading zone, fully dimensioned (DS) 2-02.2.1.14.
c) Depict drainage patterns and finish grades on the site plan (DS 2-02.2.1.16).
d) Provide estimated cut and fill quantities (DS 2-02.2.1.17).
e) Label and dimension the right-of-way for Julian Avenue (DS 2-02.2.1.19)
f) Provide existing topographic contours at intervals not exceeding 2 feet and/or spot elevations with benchmark based on City of Tucson (COT) datum, including COT Field Book and Page numbers (DS 2-02.2.1.23).
g) Depict refuse container size and access thereto, fully dimensioned (DS 2-02.2.1.32).
h) Provide a pavement section detail or note for surfacing requirements for the refuse provision and loading zone maneuverability areas (D.S. 3-05.2.3 A and D.S. 6-01.0).
i) Demonstrate water harvesting to the maximum extent reasonably possible, in accordance with Mayor and council policy directive and the City of Tucson's Land Use Code, section 3.7.4.3 B.
j) Label existing edge of pavement and increase font size for callout note #'s 23 and 26 (see "blueline" comments on sheet AS1.0).

NOTE: A grading plan may be required for this project. Grading permit requirements are based upon earthwork (cut/fill) quantities.

Provide a revised site plan. If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.


Doug Williams
Engineering Division
Development Services Department
03/07/2003 DOUG WILLIAMS SANITATION REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
04/01/2003 CINDY AGUILAR OUT TO CUSTOMER Completed