Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03OT00307
Parcel: 117060780

Address:
213 N 4TH AV

Review Status: Completed

Review Details: SITE

Permit Number - T03OT00307
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2003 PATRICIA GEHLEN ZONING REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES DEPARTMENT
ZONING REVIEW SECTION

DATE: March 12, 2003
ACTIVITY NUMBER: T03OT00307
PROJECT NAME: Partners on 4th LLC
PROJECT ADDRESS: 213 North 4th Avenue
PROJECT REVIEWER: Patricia Gehlen

The following items must be revised on or added to the site plan. Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed:


1) The address on the site plan should match that on the site review card. Revise as required,
2) It is important to understand that Zoning certification may not be granted until the site plan is approved and all improvements are completed and inspected,
3) The site plan must demonstrate compliance with the site plan that was approved by the Board of Adjustment (C10-97-86). This is to include any improvements along 4th Avenue and in the existing parking lot and additional items listed below,
4) All landscaping shown on the B of A approved plan must be added to the site. This includes any vegetation which has already been planted but is no longer alive,
5) Revise current use under site data to "alcoholic beverage service",
6) Since this site is made up of several lots, a Pima County Lot Combo form must be submitted to Pima County and the attached lot combination covenant attached must be completed and recorded prior to approval of the site plan,
7) A "do not enter" sign must be placed at the egress location proposed along 5th Avenue,
8) The proposed pedestrian refuge which is to provide pedestrian access to the staircase in the new parking lot must be physically separated from the vehicle parking spaces adjacent to the stripping,
9) The property is current split zoned. Please revise the site data to include both zonings and the zoning line must be added to the site plan,
10) The location of the proposed PAAL may require the relocation of the dumpster, regardless of dumpster ownership. Relocation of the dumpster will require that the new dumpster location and enclosure meet current code requirements,
11) Use of the right-of-way must be approved by Department of Transportation and Real Estate,
12) Installation and inspection of perimeter outdoor lighting per the Board of Adjustment conditions is required prior to Zoning certification.
03/12/2003 PATRICIA GEHLEN NPPO REVIEW Passed
03/12/2003 PATRICIA GEHLEN LANDSCAPE REVIEW Denied See zoning comments
03/13/2003 JIM TATE SANITATION REVIEW Denied Show and label existing refuse container. Also see Engineering Folder comments.
03/13/2003 JIM TATE ENGINEERING REVIEW Denied DATE: March 13, 2003
ACTIVITY NUMBER: T03OT00307
PROJECT NAME: Partners on 4th, LLC
PROJECT ADDRESS: 213 N. 4th Ave.
PROJECT REVIEWER: James C. Tate, P.E.

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

SUBMITTAL REQUIRED: FLOOD USE PERMIT APPLICATION

1. This project is in FEMA flood hazard zone AE. A Flood Use Permit is required prior to Site Plan approval. Please provide a Flood Use Permit Application with the next Site Plan submittal.

2. Include a note on the plan that the entire site is in a FEMA Special Flood Hazard Zone AE. DS 2-02.2.1.A.15

3. Show sight-visibility-triangles at the egress to 5th Ave. DS 2-02.2.1.A.10

4. The distance from back of curb to sidewalk must be 3 ft. DS 3-01.3.3.B.1

5. Show proposed drainage patterns and spot elevations for the new parking lot.
DS 2-02.2.1.A.16

6. Show estimated cut and fill quantities. DS 2-02.2.1.A.17

7. Label and dimension the existing right-of-way for all adjacent streets. DS 2-02.2.1.A.19

8. Label and dimension from street center lines to all existing and proposed curbs and sidewalks.
DS 2-02.2.1.A.21

9. Show and label existing refuse container. DS 2-02.2.1.A.32
03/13/2003 PATRICIA GEHLEN HANDICAP-SITE REVIEW Denied Handi-cap
3/13/03
1) The number of handi-cap spaces provided must be based on the total number of vehicle spaces provided whether on-site or on-street parking. Based on the parking space provided, a minimum of six (6) spaces are required.
2) Handi-cap signage is required for each space. Please add the sign detail as required and show the location of the signage on the site plan,
3) Continuous pedestrian circulation must be provided from each handi-cap space to the existing handi-cap ramp and the sidewalk in the right-of-way along 4th Avenue.
03/13/2003 JAMES TATE FLOODPLAIN REVIEW Denied Flood Use Permit required. Also see Engineering Folder comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/10/2003 ELAINE ROSE OUT TO CUSTOMER Completed