03/05/2003 PAUL MACHADO FLOODPLAIN REVIEW Denied To: Kurt Peer
2649 N. Goyette Avenue
Tucson, Arizona, 85712

SUBJECT: 2649 N. Goyette Avenue
Floodplain use permit T03OT000411 (First Review)
T13S, R14E, Section 34


RESUBMITTAL REQUIRED: Floodplain use permit


The Floodplain use permit (FUP) cannot be approved at this time. Please address the following review comments prior to the next submittal.


Floodplain Use Permit:


1. A registered contractor or architect must submit a cost estimate. Including materials and labor.
2. The building addition cannot exceed 50% of the total value of the existing residence. Please show calculations.
3. The Base flood elevation is 2439.5. per NVGD 29 datum. The finished floor elevation shall be constructed 1' the BFE at 2440.5.
4. It will be required that a registered surveyor complete an elevation certificate prior to the issuance of a Certificate of Occupation.

If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us

Paul Machado,
Senior Engineering Associate,