Permit Number: T03OT00199
Parcel: 110080220

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T03OT00199
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2003 BLANCA ESPINO FLOODPLAIN REVIEW Denied To: Maria Edith Vasquez
2643 N. Goyette Avenue
Tucson, Arizona, 85712

SUBJECT: 2643 N. Goyette Avenue
Floodplain use permit T03OT00199 (First Review)
T13S, R14E, Section 34


RESUBMITTAL REQUIRED: Floodplain use permit


The Floodplain use permit (FUP) cannot be approved at this time. Please address the following review comments prior to the next submittal.


Floodplain Use Permit:



1. A site plan with the correct property, house dimensions and drawn to scale per COT standards is required. A sample plot plan is included with this review.
2. The Base flood elevation is 2440.0 per NVGD 29 datum. The finished floor elevation shall be 1' the BFE at 2441.0.
3. It will be required that a registered surveyor complete an elevation certificate prior to the issuance of a Certificate of Occupation.

If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us

Paul Machado,
Senior Engineering Associate,

Final Status

Task End Date Reviewer's Name Type of Review Description
04/10/2003 ELAINE ROSE OUT TO CUSTOMER Completed