Permit Number: T03OT00192
Parcel: 129120010

Address:
1221 E 26TH ST

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T03OT00192
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: Hope IV - Sites 6 & 7
REVIEWER: Doug Williams
DATE: 14 March 2003
ACTIVITY NUMBERS: T03OT00192/195


SUMMARY: Engineering Section has reviewed the revised hydrology report and floodplain use permit applications received on March 17, 2003. Floodplain approval is not recommended at this time. Please address the following comments prior to resubmittal:


HYDROLOGY REPORT:

1) Provide the elevation of the Benchmark used for this study. The consultant may wish to refer to the City Field Book referenced for a closer benchmark and/or elevation check;

2) Previous "Drainage Report" comment number 1, from the 26 February comment letter has not been sufficiently addressed. The Field Book elevations appear consistent with the contours depicted on figure 3, with little variation, yet the report relies on a 3-foot discrepancy with no apparent supporting data. The elevations utilized in the report and on the site plan are not consistent with the supporting information available and provided with the submittal. Clarify the report data and the site plans to reflect vertical data consistency for each site;


Please submit the $150.00 drainage review fee and a revised hydrology report addressing the above comments.


If you have any questions, I can be reached at 791-5550 ext. 1189 or Dwillia1@ci.tucson.az.us

Douglas Williams
Engineering Division
Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2003 TAMI ACHONG OUT TO CUSTOMER Completed