Review Details: FLOODPLAIN

Permit Number - T03OT00165
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2003 JAMES TATE FLOODPLAIN REVIEW Denied DATE: February 4, 2002
ACTIVITY NUMBER: T03OT00165 Flood Use Permit
PROJECT NAME: La Colonia Seis Apartments
PROJECT ADDRESS: 446 N. Campbell
PROJECT REVIEWER: James C. Tate, P.E.

A Flood Use Permit is denied.

Resubmittal required: Flood Use Permit application, copy of the Development Plan, Drainage Report.

The Drainage Report must establish finished floor elevations which assure that all structures in the flood plain are free from flooding during the 100-yr. event. The recommended finished floor elevations must be set at least one foot above the WSEL. Provide in the report the recommended minimum finished floor elevations for buildings 6,7, 8, and 9. These elevations will then be used to provide the required elevation certificates which will be supplied with the Flood Use Permit.