Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T03EL01981
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03EL01981 DENIED 100803 1. If timer is existing, clarify this. 2. Clarify which branch circuit conduit is existing, and which is new. 3. Identify panel and circuit number for fixtures, protection of such circuit, and loading on such circuit. In the case where a spare circuit has been created by the removal of other fixtures, specify this. 4. Show the location of the panel feeding these fixtures. 5. Have Structural Plans Examiner evaluate method of pole attachment to building. 791-5550 x1106 |