Permit Number: T03EL01981
Parcel: 11308021B

Address:
2960 N 1ST AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T03EL01981
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03EL01981 DENIED 100803
1. If timer is existing, clarify this.
2. Clarify which branch circuit conduit is existing, and which is new.
3. Identify panel and circuit number for fixtures, protection of such circuit, and loading on such circuit. In the case where a spare circuit has been created by the removal of other fixtures, specify this.
4. Show the location of the panel feeding these fixtures.
5. Have Structural Plans Examiner evaluate method of pole attachment to building.

791-5550 x1106