Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T03EL00900
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03EL00900 DENIED 8/2/04 1. New Panel B shall have a disconnecting means per NEC 225.31 and 225.32. 2. New Panel B1 shall have a disconnecting means per NEC 225.31 and 225.32. 3. Per NEC 250.32 (A) (2), specify that the grounded conductor run with the supply to Panel B be connected to the Panel B disconnecting means and to the grounding electrode system. 4. Establish a grounding electrode at Panel B1 per NEC 250.32 (A). 5. Per NEC 250.32 (A) (2), specify that the grounded conductor run with the supply to Panel B1 be connected to the Panel B disconnecting means and to the grounding electrode system. |