Permit Number: T03EL00900
Parcel: 111041840

Address:
3521 E HARDY DR

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T03EL00900
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T03EL00900 DENIED 8/2/04

1. New Panel B shall have a disconnecting means per NEC 225.31 and 225.32.
2. New Panel B1 shall have a disconnecting means per NEC 225.31 and 225.32.
3. Per NEC 250.32 (A) (2), specify that the grounded conductor run with the supply to Panel B be connected to the Panel B disconnecting means and to the grounding electrode system.
4. Establish a grounding electrode at Panel B1 per NEC 250.32 (A).
5. Per NEC 250.32 (A) (2), specify that the grounded conductor run with the supply to Panel B1 be connected to the Panel B disconnecting means and to the grounding electrode system.