Permit Number: T03EL00900
Parcel: 111041840

Address:
3521 E HARDY DR

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T03EL00900
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM00900 DENIED 2/13/04

1. It appears that the load on Circuit B1-4 should be allocated to B1-6.
2. Show location of all equipment in plan view, on a scaled drawing.
3. Show the Grounding Electrode System at the new service, and the sizing of its components.
4. Indicate utility available fault current and show fault calculations for AFC at panels.