Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T03EL00455
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/13/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Provide copy of approval from State Office of Manufacturer Housing. 2. Provide electrical design for service, metered disconnect, and panelboard, along with load calculations, fault calculations, fault rating of equipment, and grounding diagram. 3.Obtain approval from Planning and Engineering before resubmittal for electrical permit approval. |