Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03EL00166
Parcel: 113090180

Address:
882 E GLENN ST

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T03EL00166
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2003 REYES ARVAYO ELECTRICAL-COMMERCIAL REVIEW Approved