Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05923
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2004 | Bruce Stevens | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS PROJECT #T03CM05923 02/04/2004 7201 E. 42ND ST. THE SECOND PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS & CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION PLANS: 1. NOTE ON THE DRAWINGS THE ALLOWABLE SOIL BEARING PRESSURE USED IN THE DESIGN OF THE FOOTINGS, OR STATE THAT THE ASSUMED VALUE OF 1500 PSF IS BEING USED, PER TABLE R401.4.1, A SOILS REPORT IS NOT REQUIRED. IT IS UP TO THE DESIGNER/HOMEBUILDER TO BE AWARE OF THE SOIL AND CONDITIONS OF THE SITE. IF SOIL TESTING HAS BEEN DONE, A COPY OF THE SOILS REPORT SHALL BE SUBMITTED WITH THE CONSTRUCTION PLANS, AND THE FOUNDATION DESIGN SHALL REFLECT THE SOILS REPORTS RECOMMENDATIONS. FLOOR PLANS: 1. IDENTIFY ALL ROOMS AND SHOW DIMENSIONS ON PLAN. MINIMUM HORIZONTAL DIMENSION OF ANY HABITABLE ROOM IS 7 FT. ELEVATIONS: 1. PROVIDE COMPLETE DRAWINGS OF ALL EXTERIOR ELEVATIONS. SECTIONS - DETAILS - MISC. NOTES: 1. ADD #3 STURRUPS AT THE WINDOW AND DOOR HEADERS PER ICBO REPORT ER4203. THESE MUST BE SHOWN WITH ENDS HOOKED ON YOUR DETAIL. MECHANICAL PLANS: 1. SHOW SIZE AND LOCATION OF RETURN AIR GRILLE. ELECTRICAL PLANS: 1. NOTE THE LOCATION AND TYPE OF THE 200 AMP MAIN PANEL. NOTE THE GROUNDING AND BONDING METHOD. 2. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED OUTLET BOXES SHALL BE USED, PER E4001.6. 3. SUBMIT ELECTRICAL RISER DIAGRAM FOR 200 AMP MAIN PANEL. THIS MUST INCLUDE THE GROUNDING METHOD TO BE USED. 4. GROUNDING METHOD USED FOR THE 60AMP SUB PANEL MUST BE CALLED OUT ON PLAN. MODEL ENERGY CODE: 1. PROVIDE MODEL ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11. 2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: BRUCE STEVENS @ 791-5550 - EXT. 1344 NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC WITH THE EXCEPTION OF THE PLUMBING PORTION WHICH HAS BEEN REPLACED WITH THE ARIZONA STATE PLUMBING CODE. ALL MODEL PLANS SHALL REFERENCE THESE CODES. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2004 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 02/05/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |