Permit Number: T03CM05907
Parcel: 128150860

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM05907
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2004 GERRY KOZIOL WWM REVIEW Approved
01/16/2004 Terry Stevens BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM05907
1/16/04
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. NOTE ON THE DRAWINGS THE ALLOWABLE SOIL BEARING PRESSURE USED IN THE DESIGN OF THE FOOTINGS,
OR STATE THAT THE ASSUMED VALUE OF 1500 PSF IS BEING USED, PER TABLE R401.4.1, A SOILS REPORT IS
NOT REQUIRED. IT IS UP TO THE DESIGNER/HOMEBUILDER TO BE AWARE OF THE SOIL AND CONDITIONS OF
THE SITE. IF SOIL TESTING HAS BEEN DONE, A COPY OF THE SOILS REPORT SHALL BE SUBMITTED WITH THE
CONSTRUCTION PLANS, AND THE FOUNDATION DESIGN SHALL REFLECT THE SOILS REPORTS
RECOMMENDATIONS.

2. INDICATE THE SLOPE FOR EXTERIOR SLABS, PER R312.

3. MIN. WIDTH FOR LANDINGS AT A DOOR IS 3'.

FLOOR PLANS:

1. PROVIDE FLOOR PLAN FOR EXISTING ROOMS ADJACENT TO NEW CONSTRUCTION.

2. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS FOR ROOMS ADJACENT TO NEW CONSTURCTION.

3. PROVIDE THE LOCATIONS OF TEMPERED GLASS PER R308.4.--------REQUIRED AT UTILITY ROOM WINDOW WHICH IS WITH IN 24" OF THE DOOR

4. MIN. AREA OF A HABITAL ROOM IS 70 SQ. FT. --------BEDROOM ADJACENT TO UTILITY ROOM DOES NOT COMPLY.

5. SHOW COMPLIANCE WITH R310 PROVIDING EGRESS FROM BEDROOMS.
- MAXIMUM SILL HEIGHT OF 44"
- MINIMUM NET CLEAR AREA OF OPENING OF 5.7SF.
- MINIMUM NET CLEAR DIMENSIONS OF OPENING OF 24" HEIGHT BY 20" WIDTH.

AS SHOWN BEDROOM WINDOWS DO NOT COMPLY

6. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

7. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A
LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2

8. LOCATE AND IDENTIFY BRACED WALL TYPES AND LOCATIONS. REQUIRED AT NO LESS THAN 25' ON CENTER.

STRUCTURAL PLANS:

1. DETAIL GABLE END BRACING CONNECTIONS.

2. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE
MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF
SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF
LOWER TRUSSES.

ELEVATIONS:

1. NOTE AND SPECIFY A COMPLETE ROOFING SYSTEM: ROOFING TYPE, GRADE OF MATERIALS AND METHOD OF
INSTALLATION PER R905.

2. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

3. FOAM INSULATION: CLARIFY YOUR COMPLIANCE WITH R318 ON THE MAIN WALLS AND THOSE WALLS TO
THE ATTIC PER R318.2.3.

PLUMBING PLANS:

1. NOTE AND SPECIFY ALL PIPING MATERIALS.-------------ABS IS NOT ALLOWED FOR POTABLE WATER

2. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE, BTU DEMAND OF EACH APPLIANCE, SIZE OF
EACH BRANCH, TOTAL DEMAND & TOTAL DEVELOPED LENGTH FROM METER TO MOST REMOTE
APPLIANCE ON THE SYSTEM PER UPC 1217.2
AS INDICATED GAS LINES ARE UNDER SIZED-----------CLEARLY INDICATE WHERE GAS LINES ARE ON A PLAN VIEW

3. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH
IS MAIN WATER LINE FOR ADDITION ATTACHING TO THE WATER METER OR TO EXISTING SUPPLY?

4. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS
AND SHOWERHEADS 3 GALLONS PER MINUTE.

5. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

6. THE CITY OF TUCSON HAS NOT ADOPTED THE PLUMBING SECTION OF THE IRC 2OOO. THE CURRENT CODE BEING USED IS THE 1994 UPC WITH THE STATE AMENDMENTS. ALL PLANS MUST REFERENCE TO THIS CODE.

MECHANICAL PLANS:

1. IS THE GAS PACK JUST A FURNACE OR IS IT ALSO AN A/C UNIT? IF AN A/C UNIT THE ELEC. LOAD CALCS. ARE WRONG AS WELL AS THE PANEL SCHEDULE. AN A/C WOULD REQUIRE MORE THAN 1 2O AMP CIRCUIT.

2. INDICATE THE SIZE OF RETURN AIR DUCT TO ALL REGISTERS.

3. GAS APPLIANCES SHALL COMPLY WITH 1994 UPC WITH STATE AMENDMENTS FOR COMBUSTION AIR REQUIREMENTS. DETAIL HOW.-----------MISSING AT WATER HEATER

ELECTRICAL PLANS:

1. AT LEAST ONE WALL SWITCH CONTROLLED LIGHT MUST BE PROVIDED AT OUTDOOR ENTRANCES OR EXITS PER E3801.---------MISSING AT LAUNDRY ROOM

2. INDICATE CHANGES FOR A/C ON ELEC. PLAN

3. A 11OV RECEPT AT WATER HEATER? DO YOU MEAN 220V FOR OPTIONAL ELEC. WATER? IF SO MUST BE INCLUDED IN ELEC. CALCS. AND PANEL SCHEDULE.

4. INDICATE THE LOCATION OF ALL AIR CONDITIONING AND HEATING UNITS, AIR HANDLERS, COMPRESSORS
AND DISCONNECTS.

5. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.
6. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH
BATTERY BACKUP.
SMOKE DETECTORS ARE REQUIRED AT THE ACCESS TO ALL BEDROOMS-------MISSING IN FAMILY ROOM

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.
CALCS. PROVIDED ARE INCORRECT -------SEE ATTACHED MEC CHECK
A SHORT FORM FOR ADDITIONS CAN BE OBTAINED AT THE RESIDENTIAL COUNTER

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2004 MONICA VALDEZ OUT TO CUSTOMER Completed
01/20/2004 ANGIE SHOFFSTALL REJECT SHELF Completed