Permit Number: T03CM05905
Parcel: 13355231A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05905
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Calculate the water demand using the public fixture units shown in Tables 6-3 or A-2. Reference Section 610.3, UPC 1994.
2. Based on the water calculations submitted (provided by the landlord's engineer), the ¾" water supply to the new restrooms is undersized. Revise the pipe sizes as required to accommodate the calculated friction pressure drop of 5.5 psi/100 feet.
3. Calculate the size of the waste water pipes using the fixture units shown in Table 7-3. Reference Section 702.0, UPC 1994.
03/03/2004 EGRANT1 WWM REVIEW Passed
03/03/2004 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review
03/03/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2004 EGRANT1 OUT TO CUSTOMER Completed