Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05905
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/23/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Calculate the water demand using the public fixture units shown in Tables 6-3 or A-2. Reference Section 610.3, UPC 1994. 2. Based on the water calculations submitted (provided by the landlord's engineer), the ¾" water supply to the new restrooms is undersized. Revise the pipe sizes as required to accommodate the calculated friction pressure drop of 5.5 psi/100 feet. 3. Calculate the size of the waste water pipes using the fixture units shown in Table 7-3. Reference Section 702.0, UPC 1994. |
03/03/2004 | EGRANT1 | WWM | REVIEW | Passed | |
03/03/2004 | EGRANT1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
03/03/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/03/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |