Permit Number: T03CM05834
Parcel: 106010540

Address:
457 E KNOX DR

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM05834
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2004 Bruce Stevens BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS PROJECT #T03CM05834
01/09/2004 457 E. KNOX DR.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.
GENERAL REQUIREMENTS:
1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.
2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.
FLOOR PLANS:
1. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER P2710 WITH CERAMIC TILE, OR A LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2
STRUCTURAL PLANS:
1. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. 10 FT CANTELEVERED PORTION OF ROOF WILL REQUIRE ENGINEERED DESIGN. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA.
2. SPECIFY LATERAL SUPPORT OF TRUSSES.
3. DETAIL GABLE END BRACING CONNECTIONS.
4. DETAIL OVERFRAMED PORTION OF ROOF. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREA (>30 S.F.).
5. DETAIL CONNECTION OF TRUSSES TO TOP PLATE.
6. NOTE AND DETAIL TIE STRAPS FRAMING ANCHORS AND JOIST HANGERS BY TYPE, SIZE AND REQUIRED ATTACHMENT TO FRAMING MEMBERS.
7. SHOW DETAILS FOR BEARING AND CONNECTION AT THE 10 FT CANTELEVERED PORTION OF ROOF.
ELEVATIONS:
1. INDICATE SIDING MATERIALS TO BE USED AT GABEL ENDS.
2. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL VENTS NEEDED TO COMPLY. AT LEAST 20% OF THE VENTS MUST BE IN THE LOWER PORTION OF ATTIC (BIRD BOARDS OR SOFFIT VENTS).
SECTIONS - DETAILS - MISC. NOTES:
1. MASONRY LINTLES REQUIRE AN ENGINEERED DESIGN. AS AN ALTERNATE, MANUFACTURED STEEL LINTLES OR ANGLE IRON LINTLES AS SPECIFED BY CODE CAN BE USED.
PLUMBING PLANS:
1. NOTE THAT COPPER WATER LINES UNDER SLAB MUST BE CONTINUOUS WITHOUT CONNECTIONS UNDER SLAB.
2. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE (INCLUDING EXISTING). THE LISTED BTU DEMAND AT 90 FT LENGTH WILL REQUIRE AT LEAST AN 1-1/4" FEED FROM THE METER PER UPC 1217.2
3. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS AND SHOWERHEADS 3 GALLONS PER MINUTE.
4. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER. MUST DISCHARGE AT EXTERIOR BETWEEN 6" AND 24" ABOVE GRADE, AND MUST TERMINATE FACING DOWN.
5. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.
6. THE CITY OF TUCSON HAS ADOPTED THE 1994 UNIFORM PLUMBING CODE WITH THE STATE AMENDMENTS (ARIZONA STATE PLUMBING CODE). ALL PLANS MUST REFERENCE THIS CODE.
ELECTRICAL PLANS:
1. INDICATE THE LOCATION OF CONVENIENCE OUTLET AND EQUIPMENT DISCONNECT FOR ROOF MOUNTED HEATING AND AIR CONDITIONING EQUIPMENT PER E3801.11 AND E3803.4.
2. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.
3. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.
4. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH BATTERY BACKUP. WHEN CEILING FINISH MATERIALS ARE REMOVED, EXISTING BEDROOMS SHALL BE IN COMPLIANCE. WHEN CEILING FINISH MATERIALS ARE NOT REMOVED, EXISTING BEDROOMS SHALL BE EQUIPED WITH BATTERY OPERATED SMOKE DETECTORS PER R317.1.1.
IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
BRUCE STEVENS @ 791-5550 EXT. 1174

NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC WITH THE EXCEPTION OF THE PLUMBING PORTION WHICH HAS BEEN REPLACED WITH THE ARIZONA STATE PLUMBING CODE. ALL MODEL PLANS SHALL REFERENCE THESE CODES.
12/22/2003 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2004 TAMI ACHONG OUT TO CUSTOMER Completed
01/09/2004 TAMI ACHONG REJECT SHELF Completed