Review Details: RESUBMITTAL
Permit Number - T03CM05828
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/02/2004 | Neil Saunders | BUILDING-RESIDENTIAL | REVIEW | Denied | T03CM05828 Turner Remodel 1. Provide design of corner window assembly by registrant. Structural Loads need to be quantified and justified. 2. Clarify G.L.B. Detail 5/5 notes a 5 1/8" x 11 1/2 G.L.B while the submitted calculation notes (2) 1.75"x12". Which member is being used? 3. Deferred submital is at the discretion of the building official. Please provide truss calculations, include calculations for the girder truss. 4. Resubmit 2 new copies of plans (minus the zoning and floodplain approved, page 1). Drawings with red ink annotations are not adequate for our records or as approved plans. ANY QUESTIONS PLEASE CONTACT NEIL SAUNDERS @ 791-5550 x2208 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/03/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 02/03/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |