Permit Number: T03CM05828
Parcel: 10824016E

Address:
4111 N CACTUS BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05828
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2004 Neil Saunders BUILDING-RESIDENTIAL REVIEW Denied T03CM05828
Turner Remodel

1. Provide design of corner window assembly by registrant. Structural Loads need to be quantified and justified.

2. Clarify G.L.B. Detail 5/5 notes a 5 1/8" x 11 1/2 G.L.B while the submitted calculation notes (2) 1.75"x12". Which member is being used?

3. Deferred submital is at the discretion of the building official. Please provide truss calculations, include calculations for the girder truss.
4. Resubmit 2 new copies of plans (minus the zoning and floodplain approved, page 1). Drawings with red ink annotations are not adequate for our records or as approved plans.

ANY QUESTIONS PLEASE CONTACT NEIL SAUNDERS @ 791-5550 x2208

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2004 TAMI ACHONG OUT TO CUSTOMER Completed
02/03/2004 ANGIE SHOFFSTALL REJECT SHELF Completed