Permit Number: T03CM05828
Parcel: 10824016E

Address:
4111 N CACTUS BL

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM05828
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2004 Neil Saunders BUILDING-RESIDENTIAL REVIEW Denied Residential Plan Review Justin Turner Residence T03CM05828


General Requirements

1. Provide square footage for existing residence.

Site Plan

1. Note locations of gas, water and electric lines.

Foundation Plans

1. Division 2 - Sitework : "Minimum design allowable soil bearing pressure - 1000 psi". 2000 IRC requires the allowable soil bearing pressure to be no less than 1500 psi. Modify plans to comply with table R401.1.1.
2. Supply scales on all details
3. Note footing width, anchor bolt size and the minimum 12" depth into undisturbed soil on details 8, 9, 12 & 13.

Structural Plans

1. Clarify whether power steel lintel or lintels that are called out on roof framing plan at the corner window will be used. Provide detail on how the ¼" plate steel will connect to wall on either side of the window. Show how 2-2x12's will be attached to the ¼" plate steel.
2. Concrete veneers are unsatisfactory. Reference R703.7 for compliance (1" air space)
3. If b1, existing beam is (2) 2x12 then it is inadequate to support existing and new roof. Clarify beam size and justify loads.
4. Provide truss calculations, include calculations for Girder Truss

Elevations

1. Provide attic ventilation in compliance with R806.2.

Details - Sections - Misc

1. Detail 12: Note treated wood for sill plate.

Plumbing Plans

1. Gas calculations are good, but reference table 12-3 of the 1994 UPC.
2. Note on plan compliance with water conservation: sinks - 3 gallons per minute.

Mechanical Plan

1. Note on Plans: Mechanical shall comply with chapters 12-16 and 18-24 2000 IRC.

Electrical Plan

1. Ceiling fan : provide a note indicating only approved outlet boxes shall be used, per E4001.6.
2. Label two rooms adjacent to kitchen. New Panel K and cannot be located in closets or bathrooms.

ANY QUESTIONS CONTACY NEIL SAUNDERS @ 791-5550 x2208

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
01/15/2004 ANGIE SHOFFSTALL REJECT SHELF Completed