Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05820
Parcel: 11941176H

Address:
1747 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05820
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2004 JIM EGAN FIRE REVIEW Approved
01/27/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T03CM05820 DENIED 01/20/04
1. Provide disconnect for water heater per NEC 422 Part C. This comment was made on 12/19/03. Provide such disconnect, lock-out CB, or justify otherwise.
2. Considering that sign circuits are expected to operate continuously, they should be subjected to a 1.25 demand factor. WH is listed at 3VA on panel schedule but is only 1.6 KW on Electric Load Summary. It appears that this panel is loaded to 84 amps, larger than 75A. Please clarify/correct.

Please call Linda Buczynski at 791-5550 x1106, or email at lbuczyn1@ ci.tucson.az.us if you have any questions.
01/27/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved