Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2004 JIM EGAN FIRE REVIEW Approved
01/20/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/20/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/20/2004 JEGAN BUILDING-COMMERCIAL REVIEW Approved
01/27/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T03CM05819 DENIED 01/20/04
1. Provide disconnect for water heater per NEC 422 Part C. This comment was made on 12/19/03. Provide such disconnect, lock-out CB, or justify otherwise.
2. Considering that sign circuits are expected to operate continuously, they should be subjected to a 1.25 demand factor. WH is listed at 3VA on panel schedule but is only 1.6 KW on Electric Load Summary. It appears that this panel is loaded to 80 amps, larger than 72A. Please clarify/correct.

Please call Linda Buczynski at 791-5550 x1106, or email at lbuczyn1@ ci.tucson.az.us if you have any questions.