Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05819
Parcel: 11308001A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05819
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2004 DROBEY1 FIRE REVIEW Approved
01/20/2004 GERRY KOZIOL WWM REVIEW Approved
01/20/2004 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
12/19/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide complete plumbing plan, including water and waste riser diagrams. Reference Section 103.2.3, UPC 1994.
12/19/2003 DAN CASTRO ZONING REVIEW Approved
12/19/2003 ROBERT SHERRY WATER REVIEW Approved
12/19/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM05819 DENIED 12/19/03
1. Provide disconnect for water heater per NEC 422 Part C.
2. Indicate panel and circuit numbers for all new electrical loads on Power Plan.
3. Provide load calculations for panel.
12/19/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation for restroom per Section 403.3, IMC 2000.
12/19/2003 BLANCA ESPINO ENGINEERING REVIEW Approved