Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05819
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/20/2004 | DROBEY1 | FIRE | REVIEW | Approved | |
| 01/20/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 01/20/2004 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/19/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide complete plumbing plan, including water and waste riser diagrams. Reference Section 103.2.3, UPC 1994. |
| 12/19/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 12/19/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/19/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM05819 DENIED 12/19/03 1. Provide disconnect for water heater per NEC 422 Part C. 2. Indicate panel and circuit numbers for all new electrical loads on Power Plan. 3. Provide load calculations for panel. |
| 12/19/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation for restroom per Section 403.3, IMC 2000. |
| 12/19/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved |