Permit Number - T03CM05791
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise water and waste fixture unit calculations using public values from Tables 6-3 and 7-3, UPC 1994.
2. Include all existing fixtures in the calculations. Reference Sections 610.1 and 703.1, UPC 1994. SIze the water piping using Table 6-4, UPC 1994.
3. Provide listing information for reduced pressure backflow preventer showing the pressure/flow information.
4. Section 507, UPC 1994 as amended by the State of Arizona is the controlling code for combustion air for the water heater.
02/18/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the restroom ventilation complies with Section 403.3, IMC 2000.