Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05791
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/18/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise water and waste fixture unit calculations using public values from Tables 6-3 and 7-3, UPC 1994. 2. Include all existing fixtures in the calculations. Reference Sections 610.1 and 703.1, UPC 1994. SIze the water piping using Table 6-4, UPC 1994. 3. Provide listing information for reduced pressure backflow preventer showing the pressure/flow information. 4. Section 507, UPC 1994 as amended by the State of Arizona is the controlling code for combustion air for the water heater. |
| 02/18/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the restroom ventilation complies with Section 403.3, IMC 2000. |