Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05791
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/17/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/17/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 02/17/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 03/03/2004 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 12/17/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/17/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise water and waste fixture unit calculations using public values from Tables 6-3 and 7-3, UPC 1994. 2. Include all existing fixtures in the calculations. Reference Sections 610.1 and 703.1, UPC 1994. 3. Provide listing information for reduced pressure backflow preventer showing the pressure/flow information. 4. Provide riser diagram for waste and water supply. Reference Section 103.2.2, UPC 1994. 5. Provide detail of water heater installation showing valves, T&P relief piping, and expansion tank. Reference Section 103.2.2, UPC 1994. 6. If the water heater is not equipped with integral heat traps, insulate the first eight feet of the cold and hot water pipes. Reference Section 704.5, IECC 1998. 7. Show vent size and termination for the water heater. Reference Section 512.0, UPC 1994. 8. Provide combustion air for the water heater. Reference Section 507, UPC 1994 as amended by the State of Arizona. |
| 12/17/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/17/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/17/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the ventilation for the space complies with the requirements of Section 403.3, IMC 2000. (Pet shops require 1.0 CFM/SF) 2. Show dryer venting. Reference Section 504.6, IMC 2000. 3. Show that the restroom ventilation complies with Section 403.3, IMC 2000. |