Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T03CM05789
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/17/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 12/17/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/17/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/17/2003 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 12/17/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM05789 DENIED 12/17/03 1. Phases A & B on Panel A are overloaded. For Phase A, applying all demand factors, 15060 VA means 126 A. For Phase B, 16, 125 VA menas 134 A. Note that the receptacle loads, which do not exceed 10,000 VA, are not subject to demand factors. 2. New Panel B on Power Plan appears to be New Panel A1. Please clarify. |