Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05776
Parcel: 124061470

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05776
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
01/12/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
01/14/2004 JIM EGAN FIRE REVIEW Approved
01/22/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water pressure calculations to include a minimum pressure of 15 PSI. Revise pipe sizes as required. Reference Section 608.1, UPC 1994.
2. Revise flow rate of lavatories to comply with ARS 45-313.
3. Revise fixture unit calculations using the fixture units shown in Tables 6-3 and 7-3, UPC 1994.
4. Show route and termination of T&P relief piping from water heaters. Reference Section 608.5, UPC 1994.
5. Show how the existing 4"S terminates on the North side of the building. Show the upper terminal cleanout. Reference Section707.4, UPC 1994.
01/22/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Z_DO NOT USE
01/22/2004 ROBERT SHERRY WATER REVIEW Approved
01/22/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations for project.
2. Revise termination of condensate drains for ACU-7 and ACU-8 to avoid surface runoff.
03/16/2004 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review
03/16/2004 EGRANT1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2004 EGRANT1 OUT TO CUSTOMER Completed