Permit Number: T03CM05752
Parcel: 13615018A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05752
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2004 JIM EGAN FIRE REVIEW Approved
01/28/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Resize water meter to reduce pressure drop. Reference
Section 610.2, UPC 1994.
2. Resize booster pump to provide for the calculated demand.
3. Show installation of the booster pump and the associated piping. Provide riser diagram for the water supply system.
4. Connect the vents for the new handsink and the mop sink to the terminations of the trap arms. Reference Section 1002.4, UPC 1994
5.The size of the reduced pressure backflow preventer
must be the same as the building water supply
line. Reference Section 610.2, UPC 1994.
6. Revise water fixture units for the ice machine and the soda machines to match the values shown in Table 6-3, UPC 1994, for 3/8" water outlets.
01/28/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/30/2004 TACHONG1 WWM REVIEW Needs Review
01/30/2004 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/30/2004 TAMI ACHONG OUT TO CUSTOMER Completed