Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05752
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 01/28/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Resize water meter to reduce pressure drop. Reference Section 610.2, UPC 1994. 2. Resize booster pump to provide for the calculated demand. 3. Show installation of the booster pump and the associated piping. Provide riser diagram for the water supply system. 4. Connect the vents for the new handsink and the mop sink to the terminations of the trap arms. Reference Section 1002.4, UPC 1994 5.The size of the reduced pressure backflow preventer must be the same as the building water supply line. Reference Section 610.2, UPC 1994. 6. Revise water fixture units for the ice machine and the soda machines to match the values shown in Table 6-3, UPC 1994, for 3/8" water outlets. |
| 01/28/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/30/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 01/30/2004 | TACHONG1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/30/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |