Permit Number: T03CM05752
Parcel: 13615018A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05752
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
01/12/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/14/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Z_DO NOT USE
01/14/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Resize water meter to reduce pressure drop. Reference Section 610.2, UPC 1994.
2. Revise sizes of water pipes to match calculations. reference Section 610.5, UPC 1994.
3. The size of the reduced pressure backflow preventer must be the same as the building water supply line. Reference Section 610.2, UPC 1994.
01/14/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide total hood weight. Include weight of person woking on hood in calculations. Reference Section 507.6, IMC 2000.
2. Provide size of exhaust duct. Reference Section 506.3.5, IMC 2000.
3. Revise termination of exhaust outlet. Reference Section 506.3.13.1, IMC 2000.
01/22/2004 TACHONG1 FIRE REVIEW Needs Review
01/22/2004 TACHONG1 WWM REVIEW Needs Review
01/22/2004 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/22/2004 TAMI ACHONG OUT TO CUSTOMER Completed