Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05752
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 01/12/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 01/14/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Z_DO NOT USE | |
| 01/14/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Resize water meter to reduce pressure drop. Reference Section 610.2, UPC 1994. 2. Revise sizes of water pipes to match calculations. reference Section 610.5, UPC 1994. 3. The size of the reduced pressure backflow preventer must be the same as the building water supply line. Reference Section 610.2, UPC 1994. |
| 01/14/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide total hood weight. Include weight of person woking on hood in calculations. Reference Section 507.6, IMC 2000. 2. Provide size of exhaust duct. Reference Section 506.3.5, IMC 2000. 3. Revise termination of exhaust outlet. Reference Section 506.3.13.1, IMC 2000. |
| 01/22/2004 | TACHONG1 | FIRE | REVIEW | Needs Review | |
| 01/22/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 01/22/2004 | TACHONG1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/22/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |