| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2004 | TACHONG1 | FIRE | REVIEW | Needs Review | |
| 01/12/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 01/12/2004 | TACHONG1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/12/2004 | TACHONG1 | ENGINEERING | REVIEW | Needs Review | |
| 01/12/2004 | TACHONG1 | ZONING | REVIEW | Needs Review | |
| 12/18/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify gas piping layout shown on floor plan 1/P-1. Show sizes of connections to cooking equipment. 2. Revise Plumbing Schedule using the fixture unit values shown in Tables 6-3 and 7-3, UPC 1994. 3. Revise Water Calculations, to comply with Section 610.1, UPC 1994. The maximum velocity is limited to 5-8 feet per second in copper pipe. Reference Section A6.1, UPC 1994 and Section 610.0, IAPMO IS 3-93. 4. Revise drain and waste design to comply with Chapter 7, UPC 1994. 5. Revise location of vent for the grease trap to comply with the manufacturer's installation requirements. |
| 12/18/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM05752 DENIED 12/18/03 1. Indicate panel and circuit numbers for all electrical loads, and resubmit for full review. 2. Supply cut sheets for any outdoor lighting. |
| 12/18/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide hood and exhaust fan information. Refernce Sections 506 and 507, IMC 2000. 2. Show how the building ventilation complies with Section 403, IMC 2000. 3. Show support for the hood complies with Section 507.6, IMC 2000. 4. Provide electrical interlock with hood exhaust fan and evaporative cooler. Reference Section 508.1, IMC 2000. 5. Show plans to scale. Reference Section 106.3.1, IMC 2000. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/12/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |