Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05752
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/12/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise location of automatic gas shut off valve. 2. Clarify gas piping layout shown on floor plan 1/P-1. 3. Show location and size of water meter and reduced pressure backflow preventer. 4.Revise Plumbing Schedule using the fixture unit values shown in Tables 6-3 and 7-3, UPC 1994. 5. Revise Water Calculations, to comply with Section 610.1, UPC 1994. 6. Revise detail 3/P-1 to coordinate with the floor plan, 1/P-1. 7. Provide reduced pressure backflow preventer for water supply to the soda machine. Reference Section 603.3.12, UPC 1994. 8. Provide listing information that shows that the ice machine is equipped with an air gap or an integral backflow preventer or provide backflow protection. 9. Revise drain and waste design to comply with Chapter 7, UPC 1994. 10. Show the route and termination of the T&P relief pipe on the floor plan. 11. Provide trap and vent for the 3-compartment sink. 12. Provide vent and clean out for the grease trap. 13. Provide vent for the flow control device on the 3-compartment sink. 14. The prep sink and one compartment of the 3-compartment sink shall not be directly connected to the sanitary drain system. Reference Section 801.2, UPC 1994. |
| 12/12/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/12/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise detail 5/A-1 to comply with Section 506.3.11, IMC 2000. 2. Show how the make up air is being supplied for the Type I hood. Reference Section 508, IMC 2000. 3. Provide hood and exhaust fan information. Refernce Sections 506 and 507, IMC 2000. 4. Show how the building ventilation complies with Section 403, IMC 2000. 5. Delete Smoke Detector Note (Drawing A-1) if no mechanical air handler over 2000 CFM is on the project; Correct the note to comply with Section 606, IMC 2000 if such equipment is being installed. 6. Show support for the hood complies with Section 507.6, IMC 2000. |
| 12/18/2003 | MVALDEZ1 | FIRE | REVIEW | Needs Review | |
| 12/18/2003 | MVALDEZ1 | WWM | REVIEW | Needs Review | |
| 12/18/2003 | MVALDEZ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/18/2003 | MVALDEZ1 | ZONING | REVIEW | Needs Review | |
| 12/18/2003 | MVALDEZ1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 12/18/2003 | MVALDEZ1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/18/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |