Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05751
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/12/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
12/12/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/12/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
12/12/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
12/15/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
12/15/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM05751 DENIED 12/12/03 1. Provide load calculation Panel B. 2. Specify conductor size to feeder to Panel A in its new location. DENIED 12/15/03 1. Provide total amps on Panel B. 2. Suggest use of a spare for new load. |
12/15/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
12/15/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
12/15/2003 | ROBERT SHERRY | WATER | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/15/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |