Permit Number: T03CM05730
Parcel: 123080540

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05730
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2004 JIM EGAN FIRE REVIEW Approved
01/14/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water supply calculations per Section 610.1, UPC 1994. Include table of fixture units for all of the fixtures being supplied (Section 610.1) and the data required in Section 610.7.
2. Provide water supply isometric.
3. Provide vents for floor sinks. Reference Section 901.1, UPC 1994.
4. Provide backflow protection for all directly connected equipment that is not equipped with either a listed, integral backflow device or an air gap. Reference Section 603.0, UPC 1994.
5. Coordinate the equipment schedule with the plumbing floor plan and isometrics.
01/14/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM05730 DENIED 1/14/04
1. On Circuit A-10, Coffee Grinder is listed at 200 VA. Per the Equipment Schedule, this equipment draws 9A, which would total 1080 VA. Please clarify/correct.
2. On Circuit A-16, Dishwasher is on a 20/1 CB. Per the Equipment Schedule, this equipment is 240V, which would need a 2-P CB. Please clarify/correct, and re-evaluate VA.
3. On Circuit A-18, REf. Display Case is listed at 200 VA. Per the Equipment Schedule, this equipment draws 12A, which would total 1440 VA. Please clarify/correct.
4. Equipment Schedule lists (2) Expresso Grinders as Item #3. No power to such equipment. Please clarify/correct.
5. Provide lighting fixture schedules. This is a submittal requirement.
6. Provide Interior Lighting Power calculations per the 1998 IECC.
01/14/2004 ROBERT SHERRY WATER REVIEW Approved
01/14/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/14/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/20/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Z_DO NOT USE
01/21/2004 GERRY KOZIOL WWM REVIEW Approved
12/17/2003 CRAIG GROSS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/21/2004 LISA LESNY OUT TO CUSTOMER Completed