Permit Review Detail
Review Status: Completed
Review Details: REVISION - WALK THRU
Permit Number - T03CM05722
Review Name: REVISION - WALK THRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM05722 DENIED 4/13/04 1. #2 ampacity is 115a. This can not be protected by a 125 AF. 2. Provide rating in amps of Panel L. 3. Provide load calculations for Panel L. 4. Provide TEP available fault current, and fault calculations to show AFC at service disconnect and Panel L. 5. Provide site plan for temporary power. Indicate location of service and Panel L. |