| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/21/2004 | MVALDEZ1 | FIRE | REVIEW | Needs Review | |
| 12/29/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/29/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the HWS/R pipe sizes shown on 1/M-1 with 2/M-1. 2. A condensate drain is not an approved termination for a pressure relief pipe. Reference Section 608.5, UPC 1994. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/21/2004 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |