Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show material of construction for hydronic piping.
2. Indicate installation dimensions of roof terminal assembly.
3. Detail 2/M-2 shows a P/T relief valve. Show required pressure and temperature ratings along with the size, route, and termination of the relief piping.
4. Coordinate pipe sizes shown on details 1/M-1, 2/M-1, and 3/M-1,
12/29/2003 MVALDEZ1 FIRE REVIEW Needs Review
12/29/2003 MVALDEZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/29/2003 MONICA VALDEZ OUT TO CUSTOMER Completed