Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05709
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/09/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
12/09/2003 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
12/10/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
12/10/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/10/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/10/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/10/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the total outside air quantity to comply with Section 403.3.2, IMC 2000. 2. Provide exhaust for the new rest room and the bathroom. Reference Section 403.3, IMC 2000. |
12/10/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise riser diagram for ADA private bathroom to include adjoining bathroom and coordinate with the floor plan. 2. Clarify water piping (especially with regard to the water heater) and include riser diagram. 3. Show the complete gas piping system and indicate the developed pipe length and gas loads. 4. If the water heater does not come with integral heat traps, provide heat traps on the hot and cold water pipes and insulate the first 8 feet of hot and cold water pipes. Reference Section 704.5, IECC 2000. 5. Provide detail of water heater installation including expansion tank, T&P piping, and shut off valve. 6. Provide combustion and relief air for the water heater. Reference Section 507.0, UPC 1994, as amended by the State of Arizona. 7. Show flue for the water heater. |
12/11/2003 | GERRY KOZIOL | WWM | REVIEW | Approved |