03/29/2004 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM05700

3/29/04 2502 E. HAMPTON ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


SITE PLAN:

1.PROVIDE THE SCALE.

FOUNDATION PLAN:

1.PROVIDE A LANDING AT THE 3068 FROM THE GARAGE.

STRUCTURAL PLANS:

1. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.

SECTIONS - DETAILS - MISC. NOTES:

1. A / 1 ; SPECIFY THE LENGTH OF THE ANCHOR BOLT
DESCRIBE THE BOTTOM PLATE
CLARIFY THE FOOTING THICKNESS AND DEPTH
COMPLETE THE VENEER (WEEP HOLES, FLASHING, WEATHER BARRIER, SHEATHING, AIR SPACE)

2. B / 1 ; SPECIFY THE LOCATION OF THE VERTICICALS
SPECIFY THE HORIZONTAL JOINT REINFORCEMENT
CLARIFY THE FOOTING THICKNESS AND DEPTH

3. C / 1 ; ILLUSTRATE THE THIRD CONTINUOUS REBAR THROUGH THE PIN FOOTING

4. B / 3 ; THE PLYWOOD IS REQUIRED TO HAVE EXTERIOR GLUE WHERE EXPOSED TO THE WEATHER
ARE THE WALL TIES ON EACH STUD?
PROVIDE A TRUSS / WALL CONNECTION

5. 1 / 4 ; HU26 APPEARS TO BE INADEQUATE

6. FRAMING NOTE 1 / 4 ; SPECIFY THE LUMBER SPECIES

7. PROVIDE THE DESIGN LOADS.

8. SECTION A / 5 ; THE INSULATION IN THE WALLS APPEARS TO CONFLICT WITH THE M.E.C. STATEMENT

PLUMBING PLANS:

1. THE "NEW FIXTURE UNITS" CHART APPEARS TO BE INACCURATE.

2. PLEASE RE-CHECK THE SIZE OF THE WATER SERVICE LINE AND THE WATER DISTRIBUTION SYSTEM.

3. IF THE WATER HEATER IS GAS, PROVIDE GAS.

ELECTRICAL PLANS:

1. THE MINIMUM SIZE FOR A HOUSES SERVICE IS 100 AMPS.

2. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT THE BACK OF THE DWELLING, PER E3801.7. THESE OUTLETS SHALL BE GFI PROTECTED PER E3802.3.

3. IF THE WATER HEATER IS ELECTRIC, PROVIDE A CIRCUIT.

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. JUSTIFY THE WINDOW U-VALUE.