Permit Number: T03CM05698
Parcel: 11303083D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05698
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2003 JIM EGAN FIRE REVIEW Approved
12/09/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/09/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
12/09/2003 ROBERT SHERRY WATER REVIEW Approved
12/09/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
12/09/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved ok
12/09/2003 JIM TATE ENGINEERING REVIEW Approved
12/10/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved t03cm05698 DENIED 12/10/03
1. Show fault calculations, AFC at new Panels, and demonstrate that rating of panels is sufficient.
2. Fuse the disconnects for the new panels. Feeders are not protected.
3. Ampacity of #6 is only 65A. Feeders appear insufficient. Re-evaluate conductor and conduit size
12/30/2003 GERRY KOZIOL WWM REVIEW Approved