Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05697
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/09/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/09/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/09/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/09/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/09/2003 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/09/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | Revise ventilation quantities for areas ventilated by common air handlers. |
| 12/09/2003 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 12/11/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | t03cm05697 DENIED 12/10/03 1. Show fault calculations, AFC at new Panels, and demonstrate that rating of panels is sufficient. 2. Fuse the disconnects for the new panels. Feeders are not protected. 3. Ampacity of #6 is only 65A. Feeders appear insufficient. Re-evaluate conductor and conduit size. |
| 12/30/2003 | GERRY KOZIOL | WWM | REVIEW | Approved |