Permit Number: T03CM05696
Parcel: 110050380

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05696
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/09/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/09/2003 ROBERT SHERRY WATER REVIEW Approved
12/09/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide smoke detector in return duct of heat pump (over 2000 cfm)
2. Recalculate ventilation quantity from heat pump to provide for common areas.
12/10/2003 JIM EGAN FIRE REVIEW Approved
12/18/2003 TACHONG1 WWM REVIEW Needs Review
12/18/2003 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review
12/18/2003 TACHONG1 ZONING REVIEW Needs Review
12/18/2003 TACHONG1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2003 TAMI ACHONG OUT TO CUSTOMER Completed