Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05693
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/09/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/09/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water pressure calculations 2. Provide riser diagram for new fixtures. |
| 12/09/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM05693 DENIED 12/9/03 1. Provide water heater disconnect per NEC 422 Part C. 2. Circuit 22 on panel schedule indicates Water Heater/Bath. This circuit powers receptacles on the Power Plan. Please clarify. 3. New Track lighting is shown on Circuits 8 and 10 on panel schedule. On power Plan is Circuits 6 and 8. Please clarify. 4. Electrical Note 10 is not appropriate for a commercial project, as NEC 210-52 pertains to Dwelling Unit Receptacle outlets. Clarify intent. 5. Electrical Note 11 is not appropriate for a commercial project, as NEC 210-52 pertains to Dwelling Unit Receptacle outlets. Clarify intent. 6. Perform load calculations according to NEC 220 for commercial installations. Use of the 50% demand factor for receptacle loads over 10,000 VA is only applicable to receptacle loads computed at no more than 180 VA per outlet, or multi-outlet assemblies. Items such as water heaters not to be included when applying this demand factor. See NEC 220-13. 7. Clarify load calculations to Panel C which call for such loads as the 50A 240V circuit to be 8800 watts. Perform these calculations according the NEC Article 220 for Feeders and Services Part B. |
| 12/09/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/09/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show exhaust requirements for new rest room. |
| 12/12/2003 | MVALDEZ1 | ZONING | REVIEW | Needs Review | |
| 12/12/2003 | MVALDEZ1 | WWM | REVIEW | Needs Review | |
| 12/12/2003 | MVALDEZ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/12/2003 | MVALDEZ1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/12/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |