Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05693
Parcel: 10604299E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05693
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2003 JIM EGAN FIRE REVIEW Approved
12/09/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water pressure calculations
2. Provide riser diagram for new fixtures.
12/09/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM05693 DENIED 12/9/03
1. Provide water heater disconnect per NEC 422 Part C.
2. Circuit 22 on panel schedule indicates Water Heater/Bath. This circuit powers receptacles on the Power Plan. Please clarify.
3. New Track lighting is shown on Circuits 8 and 10 on panel schedule. On power Plan is Circuits 6 and 8. Please clarify.
4. Electrical Note 10 is not appropriate for a commercial project, as NEC 210-52 pertains to Dwelling Unit Receptacle outlets. Clarify intent.
5. Electrical Note 11 is not appropriate for a commercial project, as NEC 210-52 pertains to Dwelling Unit Receptacle outlets. Clarify intent.
6. Perform load calculations according to NEC 220 for commercial installations. Use of the 50% demand factor for receptacle loads over 10,000 VA is only applicable to receptacle loads computed at no more than 180 VA per outlet, or multi-outlet assemblies. Items such as water heaters not to be included when applying this demand factor. See NEC 220-13.
7. Clarify load calculations to Panel C which call for such loads as the 50A 240V circuit to be 8800 watts. Perform these calculations according the NEC Article 220 for Feeders and Services Part B.
12/09/2003 ROBERT SHERRY WATER REVIEW Approved
12/09/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show exhaust requirements for new rest room.
12/12/2003 MVALDEZ1 ZONING REVIEW Needs Review
12/12/2003 MVALDEZ1 WWM REVIEW Needs Review
12/12/2003 MVALDEZ1 BUILDING-COMMERCIAL REVIEW Needs Review
12/12/2003 MVALDEZ1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/12/2003 MONICA VALDEZ OUT TO CUSTOMER Completed